- | ====== AD Input Module: MD-HADIN4 ====== | + | ====== 4-Channel High Resolution Analog to Digital Input Module: MD-HADIN4 ====== |
- | {{ :modport:md-hadin4:md-adin4.png?700 }} | + | {{ :modport:md-hadin4:md-adin4.png?600 }} |
===== Specification ===== | ===== Specification ===== | ||
^ Item ^ Description ^ | ^ Item ^ Description ^ | ||
+ | | Channels | 4 | | ||
| Operating Temperature | -10 ~ 50 (no condensation) | | | Operating Temperature | -10 ~ 50 (no condensation) | | ||
| Operating Humidity | 35 ~ 85%RH | | | Operating Humidity | 35 ~ 85%RH | | ||
Line 28: | Line 29: | ||
The MD-HADIN4 has the benefit of a higher resolution than the MD-ADIN4, but takes longer to do the conversion. Therefore, the MD-HADIN4 may not be suitable for high frequency signals. | The MD-HADIN4 has the benefit of a higher resolution than the MD-ADIN4, but takes longer to do the conversion. Therefore, the MD-HADIN4 may not be suitable for high frequency signals. | ||
+ | |||
+ | ===== Output Values ===== | ||
+ | |||
+ | Read two 16-bit words from the MD-HADIN’s starting address to obtain the full 32-bit value. The data will be returned most significant word first. | ||
+ | |||
+ | The value returned from the MD-HADIN can be interpreted with the following algorithm: | ||
+ | |||
+ | <code C> | ||
+ | unsigned int rawData = 0; // Raw 32-bit value from the MD-HADIN | ||
+ | long value = rawData; | ||
+ | |||
+ | if ((rawData & 0x80000000) != 0) // If most significant bit is set | ||
+ | { | ||
+ | value = (rawData - 0x80000000) * -1; | ||
+ | } | ||
+ | |||
+ | if (value == -111111) | ||
+ | { | ||
+ | // Value is below the lower bound (e.g. below 1V when 1-5V mode is selected). | ||
+ | } | ||
+ | else if (value == 222222) | ||
+ | { | ||
+ | // Value is above the upper bound. (e.g. above 5V when 1-5V mode is selected). | ||
+ | } | ||
+ | else | ||
+ | { | ||
+ | // Value is between 0 and 100,000 | ||
+ | } | ||
+ | </code> | ||
===== Modbus Starting Address ===== | ===== Modbus Starting Address ===== | ||
Line 36: | Line 66: | ||
|Starting Address(base 10) | 200 | 201 | 202 | 203 | | |Starting Address(base 10) | 200 | 201 | 202 | 203 | | ||
|Starting Address(base 16) | C8 | C9 | CA | CB | | |Starting Address(base 16) | C8 | C9 | CA | CB | | ||
- | |Address (base 10) used by HMI (SCADA) | 00201 | 00202 | 00203 | 00204 | | + | |Address (base 10) used by HMI (SCADA) | 40201 | 40202 | 40203 | 40204 | |
===== Module ID (Modbus Slave Address) Assignment ===== | ===== Module ID (Modbus Slave Address) Assignment ===== | ||
Line 43: | Line 73: | ||
Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | ||
+ | |||
+ | [[modport:index|MODPORT]] |