All values below are given in base 10.
Start Address | Product name | Supported Modbus Function Codes |
---|---|---|
0-7 | MD-DIDC8 DC Input | 1 |
100-103 | MD-ADIN4 AD Input | 3 |
200-207 | MD-HADIN4 High Resolution AD Input | 3 |
300-303 | MD-THRT4 RTD Temperature Input | 3 |
Start Address | Prodcut name | Supported Modbus Function Codes |
---|---|---|
3000-3007 | MD-DOSO8 DC Source Output | 1, 5, 15 |
3100-3107 | MD-DOSI8 DC Sink Output | 1, 5, 15 |
3200-3207 | MD-DORL8 Relay Output | 1, 5, 15 |
3300-3301 | MD-DAOUT2 AD Output (Voltage) | 3, 6, 16 |
3400-3401 | MD-DAOUT2B AD Output (Current) | 3,6, 16 |
http://www.comfilewiki.co.kr/en/lib/images/toolbar/image.png On the front of the module, there is a rotary switch labeled ID, that is used to select the Modbus slave address for the module. When installing multiple modules of the same type, the ID for each module should be unique.
Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect.