User Tools

Site Tools

한국어

comfilehmi:hmi_connection_modbus_tcp:index

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
comfilehmi:hmi_connection_modbus_tcp:index [2024/02/01 13:12]
COMFILE Technology
comfilehmi:hmi_connection_modbus_tcp:index [2024/02/01 13:13] (current)
COMFILE Technology [Using the ComfileHMI as a Modbus TCP Server (Slave)]
Line 12: Line 12:
 There are many ways to configure a TCP/IP network, but the image above illustrates a typical scenario when the ComfileHMI is operating as a Modbus TCP client (master). ​ Each Modbus TCP server (slave) will be assigned a unique IP address. ​ In the diagram above the Moacon and the Modbus TCP gateway are both operating as Modbus TCP servers. ​ However, behind the Modbus TCP gateway, there are two individually addressable PLCs:  The CUBLOC/MSB and the Modport. There are many ways to configure a TCP/IP network, but the image above illustrates a typical scenario when the ComfileHMI is operating as a Modbus TCP client (master). ​ Each Modbus TCP server (slave) will be assigned a unique IP address. ​ In the diagram above the Moacon and the Modbus TCP gateway are both operating as Modbus TCP servers. ​ However, behind the Modbus TCP gateway, there are two individually addressable PLCs:  The CUBLOC/MSB and the Modport.
  
-In the ComfileHMI Editor's //Project Properties//,​ each channel corresponds to an individual Modbus TCP server, and each channel can have one or more PLCs.  For the configuration above, the configuration may look like the image below.+In Comfile Studio's //Project Properties//,​ each channel corresponds to an individual Modbus TCP server, and each channel can have one or more PLCs.  For the configuration above, the configuration may look like the image below.
  
 {{ :​comfilehmi:​hmi_connection_modbus_tcp:​master_channel_config.png }} {{ :​comfilehmi:​hmi_connection_modbus_tcp:​master_channel_config.png }}
Line 20: Line 20:
 | {{ :​comfilehmi:​hmi_connection_modbus_tcp:​master_plc_modport.png }}     | :::                                                                    | | {{ :​comfilehmi:​hmi_connection_modbus_tcp:​master_plc_modport.png }}     | :::                                                                    |
  
-Once configured, you can address the PLCs just as you would any other PLC in the ComfileHMI editor.+Once configured, you can address the PLCs just as you would any other PLC in Comfile Studio.
  
 ===== Using the ComfileHMI as a Modbus TCP Server (Slave) ===== ===== Using the ComfileHMI as a Modbus TCP Server (Slave) =====
  
-To use the ComfileHMI as a Modbus TCP server (slave), enable the Modbus TCP server in the ComfileHMI Editor's //Project Properties//​.+To use the ComfileHMI as a Modbus TCP server (slave), enable the Modbus TCP server in Comfile Studio's //Project Properties//​.
  
 {{ :​comfilehmi:​hmi_connection_modbus_tcp:​slave_settings.png }} {{ :​comfilehmi:​hmi_connection_modbus_tcp:​slave_settings.png }}
comfilehmi/hmi_connection_modbus_tcp/index.1706760764.txt.gz · Last modified: 2024/02/01 13:12 by COMFILE Technology