User Tools

Site Tools

한국어

modport:md-adin4:index

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
modport:md-adin4:index [2023/04/29 12:04]
COMFILE Technology [Specification]
modport:md-adin4:index [2023/05/31 04:34] (current)
COMFILE Technology [4-Channel Analog to Digital Input Module: MD-ADIN4]
Line 1: Line 1:
-====== ​MD-ADIN4 ​-Analog to Digital Input Module ======+====== ​4-Channel ​Analog to Digital Input Module: MD-ADIN4 ​======
  
  
 The AD Input Modules can be wired to read voltage sources or current sources. The AD Input Modules can be wired to read voltage sources or current sources.
  
-{{ :​modport:​md-adin4:​md-adin4.png?​700 |}}+{{ :​modport:​md-adin4:​md-adin4.png?​600 |}}
  
 When reading voltages sources, the modules can be configured for a 0 ~ 10V range or a 1 ~ 5V range using the dipswitch on the side of the module. When reading voltages sources, the modules can be configured for a 0 ~ 10V range or a 1 ~ 5V range using the dipswitch on the side of the module.
Line 14: Line 14:
 {{ :​modport:​md-adin4:​dipswitch.png?​nolink |}} {{ :​modport:​md-adin4:​dipswitch.png?​nolink |}}
  
 +===== Specification =====
 +^ Item                   ^ Description ​                                                                     ^
 +| Channels ​              | 4                                                                                |
 +| Operating Temperature ​ | -10 ~ 50 (no condensation) ​                                                      |
 +| Operating Humidity ​    | 35 ~ 85%RH                                                                       |
 +| Input Resistance ​      | 20K ohms                                                                         |
 +| Input Voltage Range    | 1~5V mode: 0.5 ~ 5.5V (Single-ended) \\ 0~10V mode: -0.5 ~ 10.5V (Single-ended) ​ |
 +| Output Value           | 0 ~ 10,​000 ​                                                                      |
 +| Resolution ​            | 13.3-bit ​                                                                        |
 +| Precision ​             | ±0.1% ​                                                                           |
 +| Conversion Speed       | 30ms per channel ​                                                                |
 +| Communication Method ​  | RS485                                                                            |
 +| Packet Transmission ​   | 3ms                                                                              |
 +| Isolation Method ​      | No Isolation ​                                                                    |
  
  
Line 62: Line 76:
  
 Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect.
 +
 +[[modport:​index|MODPORT]]
modport/md-adin4/index.1682737461.txt.gz · Last modified: 2023/04/29 12:04 by COMFILE Technology