- | ====== MD-ADIN4 -Analog to Digital Input Module ====== | + | ====== 4-Channel Analog to Digital Input Module: MD-ADIN4 ====== |
The AD Input Modules can be wired to read voltage sources or current sources. | The AD Input Modules can be wired to read voltage sources or current sources. | ||
- | {{ :modport:md-adin4:md-adin4.png?700 |}} | + | {{ :modport:md-adin4:md-adin4.png?600 |}} |
When reading voltages sources, the modules can be configured for a 0 ~ 10V range or a 1 ~ 5V range using the dipswitch on the side of the module. | When reading voltages sources, the modules can be configured for a 0 ~ 10V range or a 1 ~ 5V range using the dipswitch on the side of the module. | ||
Line 14: | Line 14: | ||
{{ :modport:md-adin4:dipswitch.png?nolink |}} | {{ :modport:md-adin4:dipswitch.png?nolink |}} | ||
+ | ===== Specification ===== | ||
+ | ^ Item ^ Description ^ | ||
+ | | Channels | 4 | | ||
+ | | Operating Temperature | -10 ~ 50 (no condensation) | | ||
+ | | Operating Humidity | 35 ~ 85%RH | | ||
+ | | Input Resistance | 20K ohms | | ||
+ | | Input Voltage Range | 1~5V mode: 0.5 ~ 5.5V (Single-ended) \\ 0~10V mode: -0.5 ~ 10.5V (Single-ended) | | ||
+ | | Output Value | 0 ~ 10,000 | | ||
+ | | Resolution | 13.3-bit | | ||
+ | | Precision | ±0.1% | | ||
+ | | Conversion Speed | 30ms per channel | | ||
+ | | Communication Method | RS485 | | ||
+ | | Packet Transmission | 3ms | | ||
+ | | Isolation Method | No Isolation | | ||
Line 62: | Line 76: | ||
Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | ||
+ | |||
+ | [[modport:index|MODPORT]] |