Line 1: Line 1:
-====== Analog Voltage Output Module: MD-DAOUT2 ======+====== ​2-Channel Digital to Analog Voltage Output Module: MD-DAOUT2 ======
  
-{{ :​modport:​md-daout2:​md-daout2.png?​700 }}+The MD-DAOUT2 is a 2-channel digital to analog voltage, 0~5V / 0~10V, output module. 
 +The voltage range is configured using the dipswitch on the side of the module. 
 + 
 +{{ :​modport:​md-daout2:​md-daout2.png?​550 }} 
 + 
 +===== Specification ===== 
 +^ Item                     ^ Description ​                           ^ 
 +| Channels ​                | 2                                      | 
 +| Operating Temperature ​   | -10 ~ 50℃ (no condensation) ​           | 
 +| Operating Humidity ​      | 35 ~ 85%RH                             | 
 +| Input Resistance ​        | 20KΩ ​                                  | 
 +| Analog Output ​           | DC 0~5V Or 0~10V (1KΩ or higher load)  | 
 +| Output Value             | 0 ~ 60,​000 ​                            | 
 +| Conversion Speed         | 30ms per channel ​                      | 
 +| Communication Method ​    | RS485                                  | 
 +| Maximum Conversion Rate  | 0 ~ 60,000, 600ms                      | 
 +| Isolation Method ​        | No Isolation ​                          | 
 + 
 +===== Output Voltage ===== 
 + 
 +Values between 0 ~ 60,000 correspond linearly to the output voltage (0 ~ 10V, dipswitch OFF / 0 ~ 5V, 
 +dipswitch ON). 
 + 
 +{{ :​modport:​md-daout2:​daout_chart.png }} 
 + 
 + 
 +===== Modbus Starting Address ===== 
 + 
 +Each module has 2 channels, each with its own unique Modbus address. 
 + 
 +^Channel ^0 ^1 ^ 
 +|Starting Address(base 10) | 3300 | 3301 | 
 +|Starting Address(base 16) | CE4 | CE5 | 
 +|Address (base 10) used by HMI (SCADA) | 43301 | 43302 | 
 + 
 +===== Module ID (Modbus Slave Address) Assignment ===== 
 + 
 +On the front of the module, there is a rotary switch labeled //ID//, that is used to select the Modbus slave address for the module. When installing multiple modules of the same type, the ID for each module should be unique. 
 + 
 +Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. 
 + 
 +[[modport:​index|MODPORT]]