This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
modport:md-daout2:index [2023/04/29 12:44] COMFILE Technology |
modport:md-daout2:index [2023/05/31 04:35] (current) COMFILE Technology [2-Channel Digital to Analog Voltage Output Module: MD-DAOUT2] |
||
---|---|---|---|
Line 1: | Line 1: | ||
- | ====== MD-DAOUT2 - 2 Channel Digital to Analog Voltage Output Module ====== | + | ====== 2-Channel Digital to Analog Voltage Output Module: MD-DAOUT2 ====== |
The MD-DAOUT2 is a 2-channel digital to analog voltage, 0~5V / 0~10V, output module. | The MD-DAOUT2 is a 2-channel digital to analog voltage, 0~5V / 0~10V, output module. | ||
The voltage range is configured using the dipswitch on the side of the module. | The voltage range is configured using the dipswitch on the side of the module. | ||
- | {{ :modport:md-daout2:md-daout2.png?700 }} | + | {{ :modport:md-daout2:md-daout2.png?550 }} |
+ | |||
+ | ===== Specification ===== | ||
+ | ^ Item ^ Description ^ | ||
+ | | Channels | 2 | | ||
+ | | Operating Temperature | -10 ~ 50℃ (no condensation) | | ||
+ | | Operating Humidity | 35 ~ 85%RH | | ||
+ | | Input Resistance | 20KΩ | | ||
+ | | Analog Output | DC 0~5V Or 0~10V (1KΩ or higher load) | | ||
+ | | Output Value | 0 ~ 60,000 | | ||
+ | | Conversion Speed | 30ms per channel | | ||
+ | | Communication Method | RS485 | | ||
+ | | Maximum Conversion Rate | 0 ~ 60,000, 600ms | | ||
+ | | Isolation Method | No Isolation | | ||
+ | |||
+ | ===== Output Voltage ===== | ||
+ | |||
+ | Values between 0 ~ 60,000 correspond linearly to the output voltage (0 ~ 10V, dipswitch OFF / 0 ~ 5V, | ||
+ | dipswitch ON). | ||
+ | |||
+ | {{ :modport:md-daout2:daout_chart.png }} | ||
+ | |||
+ | |||
+ | ===== Modbus Starting Address ===== | ||
+ | |||
+ | Each module has 2 channels, each with its own unique Modbus address. | ||
+ | |||
+ | ^Channel ^0 ^1 ^ | ||
+ | |Starting Address(base 10) | 3300 | 3301 | | ||
+ | |Starting Address(base 16) | CE4 | CE5 | | ||
+ | |Address (base 10) used by HMI (SCADA) | 43301 | 43302 | | ||
===== Module ID (Modbus Slave Address) Assignment ===== | ===== Module ID (Modbus Slave Address) Assignment ===== | ||
Line 11: | Line 41: | ||
Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | ||
+ | |||
+ | [[modport:index|MODPORT]] |