User Tools

Site Tools

한국어

modport:md-thrt4:index

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
modport:md-thrt4:index [2023/04/29 12:16]
COMFILE Technology [Temperature Input Module: MD-THRT4]
modport:md-thrt4:index [2023/05/31 04:35] (current)
COMFILE Technology [4-Channel Temperature Input Module: MD-THRT4]
Line 1: Line 1:
-====== Temperature Input Module: MD-THRT4 ======+====== ​4-Channel ​Temperature Input Module: MD-THRT4 ======
  
 +The MD-THRT4, used with a PT100Ω temperature sensor, can measure temperatures between –100 and 500 ℃ with a precision of ±0.5%.
  
- +{{ :​modport:​md-thrt4:​md-thrt4.png?​160 }}
-{{ :​modport:​md-thrt4:​md-thrt4.png?​200 }}+
  
  
 ===== Specification ===== ===== Specification =====
-^ Item                   ​^ Description ​                                                                     + Item                       Description ​                                                   ^ 
-| Operating Temperature ​ | -10 ~ 50 (no condensation) ​                                                      ​+| Channels ​                  | 4                                                               | 
-| Operating Humidity ​    ​| 35 ~ 85%RH                                                                       ​+| Operating Temperature ​     | -10 ~ 50 ℃ ((no condensation) ​                                  ​
-Input Resistance ​      20K ohms                                                                         +| Operating Humidity ​        ​| 35 ~ 85%RH                                                      
-| Input Voltage Range    ​1~5V mode: 0.5 ~ 5.5V (Single-ended\\ 0~10V mode: -0.5 ~ 10.5V (Single-ended)  ​+Sampling Rate              ​200ms per channel ​                                              
-Output Value           0 ~ 100,​000 ​                                                                     | +| Input                      RTD Sensor ​(PT100                                             
-| Resolution ​            | 16.6-bit ​                                                                        +Allowable Line Resistance  ​10Ω or less per line from the module to the temperature sensor  ​
-| Precision ​             | ±0.1                                                                           +| Precision ​                 | ±0.5                                                          ​
-| Conversion Speed       ​| 240ms per channel ​                                                               +| Conversion Speed           ​| 240ms per channel ​                                              ​
-| Communication Method ​  ​RS485                                                                            ​+| Communication Method ​      ​RS-485 ​                                                         ​
-| Packet Transmission ​   | 3ms                                                                              +| Packet Transmission ​       | 3ms                                                             ​
-| Isolation Method ​      ​| No Isolation ​                                                                    ​|+| Isolation Method ​          ​| No Isolation ​                                                   |
 ===== MD-THRT4’s Sampling Frequency ===== ===== MD-THRT4’s Sampling Frequency =====
  
Line 54: Line 54:
  
 Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect.
 +
 +[[modport:​index|MODPORT]]
modport/md-thrt4/index.1682738179.txt.gz · Last modified: 2023/04/29 12:16 by COMFILE Technology