User Tools

Site Tools

한국어

modport:md-daout2b:index

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
modport:md-daout2b:index [2023/04/27 10:03]
COMFILE Technology
modport:md-daout2b:index [2023/05/31 04:36] (current)
COMFILE Technology [2-Channel Digital to Analog Current Output Module: MD-DAOUT2B]
Line 1: Line 1:
-====== Analog Current Output Module: MD-DAOUT2B ======+====== ​2-Channel Digital to Analog Current Output Module: MD-DAOUT2B ======
  
-{{ :modport:md-daout2b:md-daout2b.png }}+The MD-DAOUT2B is a 2-channel digital to analog current, 0~20mA / 4~20mA , output module The current range is configured using the dipswitch on the side of the module
  
 +The MD-DAOUT2B’s negative terminal controls the current through a connected load; so it should not be
 +connected to a fixed potential. The MD-DAOUT2B should be used to drive differential loads. To drive single-ended loads, an isolation circuit may be required.
 +
 +
 +{{ :​modport:​md-daout2b:​md-daout2b.png?​550 }}
 +
 +===== Specification =====
 +^ Item                     ^ Description ​                                         ^
 +| Channels ​                | 2                                                    |
 +| Operating Temperature ​   | -10 ~ 50℃ (no condensation) ​                         |
 +| Operating Humidity ​      | 35 ~ 85%RH                                           |
 +| Input Resistance ​        | 20KΩ ​                                                |
 +| Analog Output ​           | 0~20mA Or 4~20mA (600Ω or higher differential load)  |
 +| Output Value             | 0 ~ 60,​000 ​                                          |
 +| Conversion Speed         | 30ms per channel ​                                    |
 +| Communication Method ​    | RS485                                                |
 +| Maximum Conversion Rate  | 0 ~ 60,000, 600ms                                    |
 +| Isolation Method ​        | No Isolation ​                                        |
 +
 +===== Output Current =====
 +
 +Values between 0 ~ 60,000 correspond linearly to the output current (4 ~ 20mA, dipswitch OFF / 0 ~ 20mA,
 +dipswitch ON).
 +
 +{{ :​modport:​md-daout2b:​daout_ch2.png }}
 +
 +===== Modbus Starting Address =====
 +
 +Each module has 2 channels, each with its own unique Modbus address.
 +
 +^Channel ^0 ^1 ^
 +|Starting Address(base 10) | 3400 | 3401 |
 +|Starting Address(base 16) | CE4 | CE5 |
 +|Address (base 10) used by HMI (SCADA) | 43401 | 43402 |
 +
 +===== Module ID (Modbus Slave Address) Assignment =====
 +
 +On the front of the module, there is a rotary switch labeled //ID//, that is used to select the Modbus slave address for the module. When installing multiple modules of the same type, the ID for each module should be unique.
 +
 +Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect.
 +
 +[[modport:​index|MODPORT]]
modport/md-daout2b/index.1682557412.txt.gz · Last modified: 2023/04/27 10:03 by COMFILE Technology