-====== Analog Current Output Module: MD-DAOUT2B ======+====== ​2-Channel Digital to Analog Current Output Module: MD-DAOUT2B ======
  
-{{ :​modport:​md-daout2b:​md-daout2b.png?​700 }}+The MD-DAOUT2B is a 2-channel digital to analog current, 0~20mA / 4~20mA , output module. ​ The current range is configured using the dipswitch on the side of the module 
 + 
 +The MD-DAOUT2B’s negative terminal controls the current through a connected load; so it should not be 
 +connected to a fixed potential. The MD-DAOUT2B should be used to drive differential loads. To drive single-ended loads, an isolation circuit may be required. 
 + 
 + 
 +{{ :​modport:​md-daout2b:​md-daout2b.png?​550 }}
  
 ===== Specification ===== ===== Specification =====
-^ Item                     ^ Description ​                           +^ Item                     ^ Description ​                                         ^ 
-| Operating Temperature ​   | -10 ~ 50℃ (no condensation) ​           +| Channels ​                | 2                                                    | 
-| Operating Humidity ​      | 35 ~ 85%RH                             ​+| Operating Temperature ​   | -10 ~ 50℃ (no condensation) ​                         
-| Input Resistance ​        | 20KΩ ​                                  ​|+| Operating Humidity ​      | 35 ~ 85%RH                                           ​
 +| Input Resistance ​        | 20KΩ ​                                                ​|
 | Analog Output ​           | 0~20mA Or 4~20mA (600Ω or higher differential load)  | | Analog Output ​           | 0~20mA Or 4~20mA (600Ω or higher differential load)  |
-| Output Value             | 0 ~ 60,​000 ​                            ​+| Output Value             | 0 ~ 60,​000 ​                                          ​
-| Conversion Speed         | 30ms per channel ​                      ​+| Conversion Speed         | 30ms per channel ​                                    ​
-| Communication Method ​    | RS485                                  +| Communication Method ​    | RS485                                                
-| Maximum Conversion Rate  | 0 ~ 60,000, 600ms                      +| Maximum Conversion Rate  | 0 ~ 60,000, 600ms                                    
-| Isolation Method ​        | No Isolation ​                          ​|+| Isolation Method ​        | No Isolation ​                                        ​|
  
 +===== Output Current =====
  
 +Values between 0 ~ 60,000 correspond linearly to the output current (4 ~ 20mA, dipswitch OFF / 0 ~ 20mA,
 +dipswitch ON).
 +
 +{{ :​modport:​md-daout2b:​daout_ch2.png }}
 +
 +===== Modbus Starting Address =====
 +
 +Each module has 2 channels, each with its own unique Modbus address.
 +
 +^Channel ^0 ^1 ^
 +|Starting Address(base 10) | 3400 | 3401 |
 +|Starting Address(base 16) | CE4 | CE5 |
 +|Address (base 10) used by HMI (SCADA) | 43401 | 43402 |
  
 ===== Module ID (Modbus Slave Address) Assignment ===== ===== Module ID (Modbus Slave Address) Assignment =====
Line 22: Line 43:
  
 Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect.
 +
 +[[modport:​index|MODPORT]]
modport/md-daout2b/index.1682740460.txt.gz · Last modified: 2023/04/29 12:54 by COMFILE Technology