 ====== 8-Channel Relay Output Moduel : MD-DORL8 ====== ====== 8-Channel Relay Output Moduel : MD-DORL8 ======
  
-{{ :​modport:​md-dorl8:​md-dorl8.png?​nolink ​|}}+{{ :​modport:​md-dorl8:​md-dorl8.png?​700 |}}
  
 This is a 4A load per channel relay output module capable of up to AC 240V.  This is a 4A load per channel relay output module capable of up to AC 240V. 
Line 8: Line 8:
  
 After prolonged used, the relay'​s mechanical contacts may become worn and will need to be replaced. ​ After prolonged used, the relay'​s mechanical contacts may become worn and will need to be replaced. ​
-(Individual relays are not available, so the entire module ​wil need to be replaed.)+(Individual relays are not available, so the entire module ​will need to be replaced.)
  
-Channel'​s starting ​address ​for DORL8 (Relay Output Module)+Each module has 8 channels, each with its own unique Modbus ​address
  
 ^Channel ^0 ^1 ^2 ^3 ^4 ^5 ^6 ^7^ ^Channel ^0 ^1 ^2 ^3 ^4 ^5 ^6 ^7^
 |Starting Address(base 10) |3200 |3201 |3202 |3203 |3204 |3205 |3206 |3207 | |Starting Address(base 10) |3200 |3201 |3202 |3203 |3204 |3205 |3206 |3207 |
 |Starting Address(base 16) | C80 | C81 | C82 | C83 | C84 | C85 | C86 | C87 | |Starting Address(base 16) | C80 | C81 | C82 | C83 | C84 | C85 | C86 | C87 |
-| Address (base 10) used by the HMI (SCADA) | 03201 | 03202 | 03203 | 03204 | 03205 | 03206 | 03207 | 03208 |+|Address (base 10) used by HMI (SCADA) | 03201 | 03202 | 03203 | 03204 | 03205 | 03206 | 03207 | 03208 |
  
-===== Module ID Adjustment ​=====+===== Module ID (Modbus Slave Address) Assignment ​=====
  
-On the front of the module, there is a rotary switch used to select the Modbus slave address for the module. When installing multiple modules of the same type, the Modbus slave address ​for each module should be unique.+On the front of the module, there is a rotary switch ​labeled //ID//, that is used to select the Modbus slave address for the module. When installing multiple modules of the same type, the ID for each module should be unique.
  
-Rotary switch position 0 corresponds to Modbus slave address 10. if the ID is changed after the power is applied, be sure to turn the Modport ​power OFF and then ON again+Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module ​is powered onit must be power cycled for the new ID to take effect. 
 + 