On the front of the module, there is a rotary switch labeled //ID//, that is used to select the Modbus slave address for the module. When installing multiple modules of the same type, the ID for each module should be unique. | On the front of the module, there is a rotary switch labeled //ID//, that is used to select the Modbus slave address for the module. When installing multiple modules of the same type, the ID for each module should be unique. | ||
Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | Rotary switch position 0 corresponds to Modbus slave address 10. If the ID is changed after the module is powered on, it must be power cycled for the new ID to take effect. | ||
+ | |||